The Yuasa SWL range has been designed as an enhanced version of the extremely popular Yuasa NPL battery type which has resulted in an improved energy to density ratio providing an impressive 40% extra discharge capacity. All other operating parameter and characteristics have remained identical, maintaining the benefit of a common mechanical and electrical design for users of both products. The Yuasa SWL range offers a further increase in choice for users of standby power products. The Yuasa SWL1100 provides a compact design resulting in an excellent power to footprint ratio, together with case material options and compliance with the high standards demanded by industry today. As with all Yuasa products, the Yuasa SWL1100 battery has a proven and well deserved reputation for excellence with those looking for a highly reliable VRLA battery power solution. 


SPECIFICATIONS
WARRANTY12 Months
NameSWL1100FR (12V 40.6Ah) Yuasa High Rate VRLA Rechargeable Battery
CodeSWL1100FR
Nominal voltage12
AH40.6
AH RATING10-min rate Constant Power to 9.6V at 20°C
DIMENSIONS
Length197
Width165
Height170
Weight14

TERMINAL TYPE
Terminal TypeM5(F)
Torque2.5
OPERATING TEMPERATURE RANGE
Storage (in fully charged condition)-20°C to +60°C
Charge-15°C to +50°C
Discharge-20°C to +60°C
STORAGE
Capacity loss per month at 20°C (approx)3
CASE MATERIAL
Standard OptionABS (UL.94:HB)
Flame retardant option (FR)ABS (UL94:V0)
CHARGING
Float charge voltage at 20°C2.275 (±1%)
Float charge voltage at 20°C2.275 (±1%)
Float Charge voltage temperature correction factor (for variations from the standard 20°C)-3
Cyclic (or Boost) charge at 20°C2.42 (±3%)
Cyclic (or Boost) charge at 20°C2.42 (±3%)
Cyclic Charge voltage temperature correction factor (for variations from the standard 20°C)-4
Cyclic (or Boost) charge current limit 9.9
MAXIMUM DISCHARGE CURRENT
1 second500
1 minute200
SHORT-CIRCUIT CURRENT & INTERNAL RESISTANCE
Internal resistance (according to EN IEC 60896-21)14.4
Short-Circuit current (according to EN IEC 60896-21)1005
IMPEDANCE
Measured at 1 kHz7.5
You may also be interested in the following products...
GS-640SHD 12V 115Ah 1000A GS Commercial Super Heavy Duty Battery
GR31 BCI, suits:Land Rover Discovery 2.5 MK 2 (1998-2004) Td5, Land Rover Defender 90 2.5 (1990-2016) Td5, Land Rover Defender 90 2.5 (1990-2016) 300... more
  • NRG Power Systems Ltd
    NRG House
    12 Hazel Drive
    Ferndown
    BH22 9SW
  • Tel: 01202 041 420
    Email: sales@nrgpowersystems.com

    Terms and Conditions
    Warranty Guide
  • Company Registered Address:
    Windrush House
    15 Marshall Avenue
    Worthing
    West Sussex
    BH14 0ES
  • Company No: 4648165
    VAT No. 801 2488 58
    © 2015 NRG Power Systems Ltd

    Powered by Pilgrim©